Stratos MAXO-Z 30/0.5-12
Typekey
Example: |
Wilo-Stratos MAXO-Z 40/0.5-8 |
Stratos MAXO |
High-efficiency pump (screw-end or flange-end pump), electronically controlled |
Z |
Single pump for domestic hot water circulation |
40/ |
Nominal connection diameter |
0.5-8 |
Nominal delivery head range [m] |
Superior intelligence, unparalleled quality.
The Wilo-Stratos MAXO-Z has specifically been developed for drinking water applications and combines the innovative characteristics of the Wilo-Stratos MAXO with a stainless steel housing. The durable and hygienic material sets it apart from other domestic hot water circulators on the market.
Premium smart-pump Wilo-Stratos MAXO-Z
High-efficiency inline glandless pump with EC motor and electronic power adjustment. Can be used for drinking water, cold water, heating water and water/glycol mixtures. Energy efficiency index (EEI) between ≤ 0.17 and ≤ 0.19 depending on pump type.
Control modes:
- Permanent, automatic performance adaptation to system requirements without setpoint specification Wilo Dynamic Adapt plus. Up to 20% energy savings compared to dp-v control mode.
- Constant temperature (T-const., factory setting)
- Constant differential temperature (dT-const.)
- Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation).
- Constant volume flow (Q-const.)
- Differential pressure control (dp-c) to a remote point in the pipe network (index circuit evaluator)
- Constant differential pressure (dp-c)
- Variable differential pressure (dp-v) with the option to set the nominal duty point
- Constant speed (n-const.)
- User-defined PID control
Functions:
- Heat quantity measurement
- Cooling quantity measurement
- Pump automatically deactivates when no flow is detected (No-Flow Stop)
- Switchover between heating and cooling mode (automatic, external or manual)
- Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
- Operating modes of twin-head pumps: Efficiency-optimised parallel operation for dp-c and dp-v, main and standby operation
- Ability to save and restore configured pump settings (3 restoration points)
- Fault and warning messages shown in plain text with advice on resolving the issue
- Pump venting function for automatic venting of the rotor chamber
- Automatic setback operation
- Automatic deblocking function and integrated full motor protection
- Dry-running detection
- Automatic detection of thermal disinfection (for domestic hot water circulation) in conjunction with a separate temperature sensor
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature
- Power consumption
- Electric consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0–10 V, 2–10 V, 0–20 mA, 4–20 mA and commercially available PT1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for operational and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CAN)
- Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; double pump operation and Wilo-Smart Gateway
- Integrated temperature sensor
- Automatic emergency operation with definable pump speed for exceptional circumstances, e.g. bus communication or sensor value malfunction
- Graphic colour display (4.3 inches) with one-button manual operation
- Use the Wilo-Assistant app to read and set operating data and –among other things– set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Cable break detection when using an analogue signal (in connection with 2–10 V or 4–20 mA)
- Outdoor installation with weather protection possible in accordance with the installation and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery:
- Pump
- Optimised Wilo-Connector
- 2x threaded cable connection M16 x 1.5
- Washers for flange screws M12 and M16 (for nominal connection diameters DN 32 to DN 65)
- 2x gaskets for threaded connection
- Thermal insulation shell
- Concise Installation and operating instructions
Optional accessories:
- ClimaForm cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CAN
- PT 1000 (B) pipe contact sensor (for domestic hot water)
- PT 1000 (AA) sensor for installation in immersion well
- Differential pressure sensor
- Smart Gateway
Technical data
- Permissible temperature range
- Drinking water up to 3.57 mmol/l (20 °dH): 0 °C to +80 °C.
- Heating water: -10 °C to +110 °C.
- Mains connection 1~230 V, 50/60 Hz
- Protection class IPX4D
- Screwed connection or flange connection (depending on type) Rp 1 to DN 65
- Max. operating pressure of standard version: 6/10 bar (special version: 16 bar)
- Max. volume flow Q: 46 m³/h
- Max. delivery head H: 12 m
- Rated Power P2: 262 W (depending on version)
- Power consumption P1 max: 295 W (depending on version)
Materials
- Bearing: Carbon-graphite
- Impeller: PPS-GF40
- Pump housing: Stainless steel
- Shaft: 1.4122, DLC-coated